Which cable and breaker to use
Put in the appliance power, the voltage and the distance from the consumer unit. You get the cable size and the breaker, following the wiring regulations.
5,500 W at 230 V draws 23.9 A. The breaker has at least 10% headroom and the cable carries 32 A, with a 0.9% voltage drop over 10 m.
Also check the appliance manual: it gives the cable and breaker the manufacturer asks for. Showers, electric taps and bathroom sockets need 30 mA RCD protection on the circuit (wiring regulations).
£350 for labour, the most common rate in the UK (£250 to £935 each).
How we work it out
Current = power ÷ voltage. Breaker = the first standard size with at least 10% headroom over the current (an appliance left on for a long time won't trip for no reason). Cable = the smallest that carries the breaker's current (copper with PVC insulation, in conduit in the wall, 2 loaded conductors, per the wiring regulations' current-carrying tables) and keeps the voltage drop to 4% or less there and back. Minimum 2.5 mm² for sockets and appliances and 1.5 mm² for lighting.